72 VEGASON 51P 53P
7 Diagnostics
7.1 Simulation
To simulate a certain filling, you can call up
the function "Simulation on the adjustment
module MINICOM, in the software program
VVO or on the signal conditioning instrument.
You simulate a vessel filling and thereby a
certain sensor current. Please note that con-
nected instruments, such as e.g. a PLC,
react according to their adjustments and will
probably activate alarms or system func-
tions.
Simulation with VVO
If you start the simulation mode with the ad-
justment program VVO on the PC, the simu-
lated level is outputted until you quit the
simulation mode.
Simulation with MINICOM
If you start the simulation mode on the adjust-
ment module MINICOM, the sensor returns to
standard operating mode after one hour.
Diagnostics
7.2 Error codes
Error codes Corrective measures
E013 No valid measured value Message is displayed during the warm-up
- Sensor in the warm-up phase phase
- Loss of the useful echo If the message remains, a false echo storage
(with the adjustment software on the PC - see
"Echo curve under "Sensor optimisation) must
be carried out together with a modification of
mounting location and orientation to achieve the
lowest possible false echo background.
E017 Adjustment span too small Carry out a readjustment.
Make sure that the difference between
min. and max. adjustment is at least 10 mm .
E036 Sensor software does not run Sensor requires a software update (service).
Message appears during a software update.
E040 Hardware failure/Electronics defec- Check all connection cables.
tive Transducer defective.
Contact our service department.