VEGASON 51P 53P 35
Electrical connection
5 Electrical connection
5.1 Connection Connection cable
Screening
Safety information Qualified person-
nel
Instruments which are not operated with
protective low voltage or DC voltage must
only be connected by qualified personnel.
This is also valid for the configuration of
measuring systems planned for Ex environ-
ment.
As a rule, do all connecting work in the com-
plete absence of line voltage. Always switch
off the power supply before you carry out
connecting work on the radar sensors. Pro-
tect yourself and the instruments.
Connection cables and bus configura-
tion
Note the Profibus specification. The connec-
tion cables must be specified for the ex-
pected operating temperatures in the plant
and must have an outer diameter of
6 12 mm, to ensure the seal effect of the
cable entry on the sensor.
For power supply and bus communication, a
two-wire cable acc. to the Profibus specifica-
tion (up to max. 2.5 mm
2
conductor cross-
section) can be used. The electrical
connection on the sensor is made by means
of spring-loaded terminals.
In a laboratory setup, a Profibus system will
also work with standard, unshielded two-wire
cable. In practice however, an automation
network and bus system can only be pro-
tected reliably against electromagnetic inter-
ference with screened cable. Acc. to the
Profibus specification (IEC 1158-2) screened
and twisted cables are prescribed.
All participants are connected in line (seri-
ally). At the beginning and end of the bus
segment, the bus is terminated by an active
bus termination. On the DP bus level, most
participants already have a bus termination
implemented. With more than 32 participants
on the DP level, a so-called repeater must be
used to open and combine another DP level
with a max. of 32 participants. On the PA bus
branch of the segment coupler, the PA ultra-
sonic sensors work also with max. 32 partici-
pants (Ex max. 10 participants).
A PA sensor can work only in conjunction with
a Profibus DP system, to which a Profibus PA
subsystem is connected. A PA Profibus par-
ticipant must consume min. 10 mA supply
current.
Connection cable and cable length
Connection cables must correspond to the
Profibus specification and the FISCO model.
The sensor cable must be in conformity with
the values of the reference cable acc. to
IEC 1158-2:
0.8 mm
2
; R
DCmax.
= 44 W/km;
Z
31.25kHz
= 80 120 W; damping = 3 dB/km;
C
asymmetric
= 2 nF/km.
The max. cable length first of all depends on
the transmission speed:
up to 94 kbit/s: 1200 m Profibus DP
up to 188 kbit/s: 1000 m Profibus DP
up to 500 kbit/s: 500 m Profibus DP
up to 1500 kbit/s: 200 m Profibus DP
up to 12000 kbit/s: 100 m Profibus DP